Customization: | Available |
---|---|
Warranty: | 12 Months O 1000 Hours |
Type: | Basic Diesel Generator |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Diesel Genset Features P.F=0.8 3Phase | ||||||||||
Generating Set Performance | 50Hz | |||||||||
Service | P.R.P | Standby | ||||||||
Rated output | kVA | 1375 | 1650 | |||||||
Active power output | kW | 1100 | 1320 | |||||||
Rated Speed | r.p.m | 1500 | ||||||||
Standard Voltage | V | 400/230 | ||||||||
Voltage available | V | 380/220 - 415/240 | ||||||||
Perforemance data refer to Standard Reference Conditions of ISO 8528:+25ºC,100m ALT,relative humidity 30% | ||||||||||
Power reduction acc.to DIN ISO 3046 Standard values:Above 100m ALT approx.1% per 100m.Above 25ºC(77ºF) approx.4% per 10ºC(50ºF). | ||||||||||
Considering cos phi=0.8 | ||||||||||
Prime Mover Performance 1500 r.p.m | ||||||||||
SERVICE | P.R.P | Standby | ||||||||
Rated output | KW | 1200 | 1429 | |||||||
Manufacturer | Cummins | |||||||||
4 stroke Diesel Engine - Injection type | Direct | |||||||||
Aspiration type | Turbocharged& Aftercooled | |||||||||
Cylinders,number and arrangement | 16 -V | |||||||||
Bore×Stroke | mm | 159X159 | ||||||||
Total Displacement | L | 50,3 | ||||||||
Cooling system | Water | |||||||||
Emission Certification | N.A | |||||||||
Compression ratio | 14.9:1 | |||||||||
Specific fuel consumption(P.R.P) | L/h | 289 | ||||||||
Specific oil consumption(at full load) | % | <0.1 | ||||||||
Total coolant capacity | L | 407 | ||||||||
Fuel System | Type | Direct Injection Cummins PT(E) | ||||||||
1.P.R.P. Prime Power - ISO 8528:PRIME POWER is the maximum power available during a variable power sequence, which may be run for an unlimited number of hours per year, between stated maintenance intervals.The permissible average power output during a 24 hours period shall not exceed 80% of the prime power.10% overload available for governing purposes only. | ||||||||||
2.Max Standby power -ISO 3046 Fuel Stop power:Power available for use at variable loads for limited annual time (500h), within the following limits of maximum operating time: 100% load 25h per year ,90% load 200h per year. No overload available. Applicable in case of failure of the main in areas of reliable electrical network. | ||||||||||
Synchronous Generator GTL | ||||||||||
Model | K1100G4 | |||||||||
Poles | num | 4 | ||||||||
Winding Conections (standard) | Star-serie | |||||||||
Insulation | class | H | ||||||||
Enclosure(according to IEC-34-5) | IP23 | |||||||||
Phases | 3+N | |||||||||
Votage Regulators | A.V.R (PMG MX341) | |||||||||
Steady voltage precision | within±1.0% from no load to full loading with cosΦ=0.8-1.0 | |||||||||
Alternator used by GTL Gensets meet the requirements of following Standard:BS5000,VDE0530,NEMA MG1-32,IEC34,CA C22.2-100,AS1359 | ||||||||||
Generationg Set Installation Data 1500 r.p.m | ||||||||||
EXHAUST SYSTEM | ||||||||||
Exhaust Gas Temperature at full load | ºC | 485 | ||||||||
ºF | 905 | |||||||||
Exhaust gas flow | L/s | 3845 | ||||||||
Maximum allowed back pressure | Kpa | 6,7 | ||||||||
AIR REQUIREMENT | ||||||||||
Air requirement for combustion at 100% load/rated speed | L/s | 1500 | ||||||||
ft3/min(CFM) | 3176,5 | |||||||||
ELECTRIC STARTING SYSTEM | ||||||||||
Standard Battery Charging System | A | 35 | ||||||||
Minimum Recommended Battery Capacity-Cold Soak @ 0 °F (-18 °C) | CCA | 1800 | ||||||||
Auxiliary voltage | V | 24 | ||||||||
LUBRICATION SYSTEM | ||||||||||
Lube oil system including sump,filters,etc. | L | 204 | ||||||||
Cold Start Capability | ||||||||||
Minimum Ambient Temp for Unaided Cold Start | °F (°C) | 45(7) |